| GAS |
RANGE |
| Acid Compounds |
0 to 3 / 10 ppm |
| Ammonia (NH3) |
0 to 100 / 300 / 1000 ppm |
| Boron Trichloride (BCl3) |
0 to 10 ppm |
| Carbon Monoxide (CO) |
0 to 100 / 300 / 1000 ppm |
| Chlorine (Cl2) |
0 to 1 / 10 / 25 ppm |
| Diborane (B2H6) |
0 to 0.5 ppm |
| Hydride (PH3) |
0 to 0.3 / 1 / 10 ppm |
| Hydrogen (H2) |
0 to 1000 / 3000 ppm |
| Hydrogen Sulfide (H2S) |
0 to 20 / 50 / 100 ppm |
| Hydrazine (N2H4) |
0 to 1 ppm |
| Nitrogen Dioxide (NO2) |
0 to 10 ppm |
| Nitrogen Monoxide (NO) |
0 to 50 ppm |
| Organic Vapours |
0 to 50 / 100 / 200 ppm |
| Oxygen (O2) |
0 to 5 / 25 / 100 Vol% |
| Ozone (O3) |
0 to 0.5 ppm |
| Sulfur Dioxide (SO2) |
0 to 10 ppm |
TECHNICAL INFORMATION
| Type |
Intrinsically safe transmitter for electrochemical sensors |
| Gases and Ranges |
Toxic gases and oxygen in various ranges |
| Output |
Analog - 4 to 20 mA |
| Maintenance signal - 3.4 mA constant |
| Fault signal - < 3.2 mA |
| Power Supply |
12 to 30 VDC, 2-wire |
| Ambient Conditions |
Transmitter only, for sensors see separate sensor data sheet |
| Temperature - – 40 to + 65 °C / – 40 to + 150 °F |
Pressure - 700 to 1300 mbar / 20.7 to 38.4 inch Hg |
| Humidity - 0 to 100 %RH, non condensing |
| Enclosure |
IP 66 / 67, NEMA 4, GRP housing |
| Size (H x W x D, approx.) |
170 x 130 x 130 mm / 6.7” x 5.1” x 5.1” |
| Weight (approx.) |
900 g / 2 lbs. |
Approvals |
| ATEX |
II 1G EEx ia IIC T6/T4: – 40 to + 40 / + 65 °C
II 3G EEx nL IIC T6/T4: – 25 to + 40 / + 65 °C |
| IECEx |
EEx ia IIC T6/T4: – 40 to + 40 / + 65 °C |
UL |
Class I, Div 1, Group A, B, C, D
Class II, Div 1, Group E, F, G
T6/T4: – 40 to + 40 / + 65 °C |
| CSA* |
Class I, Div 1, Group A, B, C, D
Ex ia T6/T4: – 40 to + 40 / + 65 °C |
CE mark |
electromagnetic compatibility (directive 89/336/EEC) |
|
*pending |
The Dräger Polytron 3000 is an intrinsically safe gas detector for the continuous monitoring of toxic gases and oxygen in ambient air. It is the first part of a new generation of gas detectors developed on a modular platform. Communication to the central control system is done via a 4 to 20 mA signal. The Dräger Polytron 3000 is available with or without display, in over 60 versions for different gases and set ranges.
Simple, quick installation The two component concept of a Docking Station and a Dräger Polytron 3000 electronics saves time and money. The Docking Station can be pre-installed – mounting and wiring it
into place separately – while protected by a rain and dust cover until commissioning. At commissioning, the Dräger Polytron 3000 electronics is fixed by a quicklock mechanism into the Docking Station, the sensor inserted - and the system is ready for operation.
Easy to operate The Dräger Polytron 3000 is easy to handle with simple maintenance procedures. The DrägerSensors are equipped with a data memory where the calibration information is stored. This allows the Dräger Polytron 3000 to either accept a precalibrated sensor, or the sensor can be calibrated with the transmitter. Digital temperature compensation of the sensor signal is automatically performed.
|